ioThinx 4530 Series Hardware Manual
Horizontal Installation
Before installing the device, ensure there is enough
space around the device so that it can dissipate heat.
In order to ensure the device works properly, we
suggest reserving the space shown in the figure below.
CAUTION
DO NOT install the device vertically, as the fan-less heat dissipation design will not perform as intended.
Powering on the Unit
After turning on the power supply, it will take 5 to 10 seconds for the operating system to boot up. The
green Ready LED will illuminate continuously until the operating system is ready.
Reset Button: Factory Reset Process
Use the following procedure to reset the ioThinx to the factory defaults. Note that when you reset the
ioThinx, all of your tag definitions, software programs, and files will be deleted, and the service and runtime
engine will be restarted.
1. Power off the device.
2. Press and hold the reset button; while holding the reset button:
a. Power on the device; the RDY LED will blink green while the device is booting up.
b. After the device has booted up, the RDY LED will blink red; continue holding the reset button until
the RDY LED stops blinking.
3. Release the reset button to load the factory default settings.
NOTE
Do NOT power off, operate, or connect any devices when the RDY LED is a solid red. The factory reset
function is only activated when the system is booting up.
NOTE
It should take about 20 seconds from the time the RDY LED starts blinking green until it stops blinking red.
3-12
Hardware Installation