4.3 Parameter Function Description

00- 00
Control mode
【0】: V/F mode
Range
【1】: SLV mode
Select the relevant control mode for the application, using parameter 00-00 Control mode.
Default control mode is V/F.
 V/F mode can be used for most applications specifically multi-motor or applications where auto
tune is not successful or when a customized V/F pattern may be required.
Several V/f patterns are available selectable by parameter 01-00.
Select the appropriate V/f pattern based on the application load type and the motor base
frequency of 50 or 60 Hz.
For selections of the V/f patterns. Refer to description of parameter 01-00
 SLV ( Sensor less vector) is used for obtaining best performance from a motor. Specially at low
speeds or for applications with dynamic speed change.
00- 01
Motor Direction Control
【0】: Forward
Range
【1】: Reverse
00 - 01 Is valid in key pad mode only.
※Note: When Reverse function is disabled by parameter 11- 00=1 setting 00-01 to 1 ." LOC" will be
displayed
00- 02
Main Run Command Source selection
00- 03
Alternative Run Command Source selection
【0】: Keypad
Range
【1】: External Run/Stop Control
【2】: Communication
Parameter 00 - 02/00- 03 sets the inverter operation command source. For switching between
00-02 and 00-03, use any of the external inputs S1 to S5 and set the relevant parameters (03-
00~03-04) to [12]. refer to parameter group3.
00- 04
Operation modes for external terminals
【0】: Forward/stop-reverse/stop
Range
【1】: Run/stop-forward/reverse
【2】: 3-wire control mode -run/stop
Parameter 00-04 sets the function of the External Run/Stop and it is used in conjunction
with Parameters .
00-02(Main Run Source) = 1 or 00-03(Alternative Run source) = 1
(When 00-02/00-03=1, the command comes from External Run /Stop)
Parameters 03-00 to 03-04, which are used to set the required function for the digital inputs [S1
to S5](multi-function inputs).
Note1: Parameters 03-00 to 03-04 are only Required for External Run/stop
(Two wire control mode).
Note2: For External Run /Stop control set parameters in the following order:
00- Basic parameter group
4-29