Siemens Sinteso FD20 Product Data page 99

Hide thumbs Also See for Sinteso FD20:
Table of Contents

Advertisement

Type
DLR1193
FDLU291
RE10
TF04
10.1.3 Technical data
Linear smoke detector FDL241-9
Operating voltage addressed / collective
Operating current (quiet) addressed / collective
Number of external alarm indicators that can
be connected
Detection distance
Operating temperature
Storage temperature
Air humidity (no moisture condensation)
Communication protocol
Conductor cross section
Color
Protection category (IEC 60529)
Standards
Approvals
VdS
LPCB
FM
System compatibility
FDnet
C-NET
Collective system compatibility
Detector heating unit DLH1191A
Operating voltage
Operating current (quiescent)
Resistance
008164_y_en_--
Designation
Reflector for short distance (foil)
Adjustment kit for linear smoke
detector
Detector tester for linear smoke
detectors
Alarm test filter (absorption 77 %)
Linear smoke detector FDL241-9
Order number
BPZ:4787840001
A5Q00004905
BPZ:3685190001
BPZ:4931090001
DC 12...33 V / DC 14...28 V
0.8 mA / 0.7 mA
10...100 m
-25...+60 °C
-30...+75°C
≤95 % rel.
FDnet or collective (with and without current limitation)
0.2...1.5 mm²
~RAL 9010 pure white
EN 54-12
, EN 54-17, EN 62471
1
(
with detection distance of 10...100 m)
1
G204063
126bd/02
3029351
FS20, AlgoRex, SIGMASYS
FS720, FC360
CZ10, BC10, FC10, XC10, CS11, FC700A, FC330A,
SIGMASYS, BMS, SM80/88/D100
DC 20...33 V
30...50 mA
Special detectors
Weight [kg]
0.025
0.840
0.345
0.005
2
IP65
600 Ω
10
99 | 152

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents