Automatic fire detectors
2
Point detector FDOOT241-9, FDOOT241-A, FDO241, FDT241
2.3.3 Technical data
Operating voltage (modulated)
Operating current (quiescent)
External alarm
Without sounder
base
indicators (EAI)
which can be
With sounder
connected
base
Communication protocol
System compatibility
Operating temperature
Storage temperature
Air humidity
Color
With detector base
FDB221/-AA,
FDB222, FDB291
Base FDB221 and
Protection
sealing element
category
FDBZ295
(IEC 60529)
Base attachment
humid FDB293 or
base attachment
wet FDB295
Standards
Approvals:
VdS
LPCB
FM
DNV GL (marine)
Permissible wind speed
20 | 152
FDOOT241-9
FDOOT241-A
65...230 μA
FD20 or collective
CZ10, CS11,
BC10, FC10,
XC10, FC330A,
FC700A, BMS,
SM80/88D100
-25...+70°C
-35...+70°C
-30...+75°C
-35...+75°C
CEA 4021, EN 54-5
EN 54-7
EN 54-27
G204007
G215052
126bh/01
3029351
1...20 m/s
¹
FS20 compatibility in FDnet is assured subject to in-country FS20 software
support.
FDO241
DC 12...33 V
180...230 μA
2
1
FDnet
FS20¹, AlgoRex, SIGMASYS
-25...+70°C
-30...+75°C
≤95 % rel.
~RAL 9010 pure white
IP43
IP44
EN 54-17
G204017
126bf/02
3029351
MEDB00003UK
FDT241
130...200 μA
-25...+50°C /
-25...+65 °C /
Depending on parameter settings
EN 54-5
G204019
126bj/02
3046115
MEDB00003UR
008164_y_en_--