Siemens Sinteso FD20 Product Data page 18

Hide thumbs Also See for Sinteso FD20:
Table of Contents

Advertisement

Automatic fire detectors
2
Point detector FDOOT241-9, FDOOT241-A, FDO241, FDT241
2.3.2.1 Accessories
Addressable detector base FDB221 / FDB221-AA
Flat, addressable detector base FDB222
Base attachment FDB291
Base attachment humid FDB293
18 | 152
You will find more information about detector bases and accessories in document
007775.
Function:
Detector base with stilts for fire detectors with addressable signal processing
'Orange' connection terminals, 0.2...1.5 mm
FDB221-AA also contains micro terminal DBZ1190-AA
Use:
For recess-mounted cable entry
For surface-mounted cable entry up to a cable diameter of 6 mm
Function:
Flat detector base for fire detectors with addressable signal processing
'Orange' connection terminals, 0.2...1.5 mm
Use:
For flush mounting; only for recess-mounted cable entry
Function:
For routing surface-mounted cables larger than Ø 6 mm
Detector base is secured with a snap fastener
For achieving a higher protection category
For mounting in wet or humid environments
Required when using detector heating unit FDBH291
Required when using protective cage DBZ1194 or EMC-protective cage
FDBZ294
Mounted between detector base and ceiling
Detector base mounted quickly: The detector base simply clicks into place in
base attachment humid FDB293.
conductor cross-section
2
conductor cross-section
2