7.1.3 Technical data
Supply
Operating voltage
Operating current (quiescent)
●
Sound activated
Sounds
Sound level
Ext. Alarm indicator (AI)
Operating temperature
Storage temperature
Air humidity
Communication protocol
Conductor cross-section on
detector base
Color
Protection category (IEC 60529)
with
●
Base FDB221 or FDB222
●
Base attachment FDB291
●
Base FDB221 and sealing
element FDBZ295
●
Base attachment humid
FDB293, base attachment wet
FDB295
Standards
Approvals
●
VdS
●
LPCB
●
FM
●
DNV GL (marine)
System compatibility FDnet
008164_y_en_--
FDS221-R, FDS221-W
DC 12...33 V
Max. 250 µA
3.5 mA
11
2 alarm levels
3 sound levels
80...99 dB(A)
2
-25...+70°C
-30...+75°C
≤95 % rel.
FDnet
According to detector base
~RAL 3000 flame red
~RAL 9010, pure white
Wall mounting with feed line
from below → IP43, otherwise IP40
IP44
IP54
EN 54-3, EN 54-17
G204073
531p
3029351
MEDB00003UV
FS20, AlgoRex, SIGMASYS
Alarm devices in the FDnet
Sounder base FDSB29x
FDSB291
FDSB292
DC 12...33 V
Max. 150 µA
1.2 mA
11
1
2 alarm levels
1 alarm level
2 sound levels
1 sound level
80...88 dB(A)
84 dB(A)
1
-25...+70°C
(observe point detector data)
-30...+75°C
≤95 % rel.
FDnet
Collective
0.2...1.5 mm
~RAL 9010, pure white
IP43
-
-
-
-
EN 54-3
G204062
531u
3029351
MEDB00003UV
FS20, AlgoRex,
SIGMASYS
7
2
-
67 | 152