Siemens Sinteso FD20 Product Data page 67

Hide thumbs Also See for Sinteso FD20:
Table of Contents

Advertisement

7.1.3 Technical data
Supply
Operating voltage
Operating current (quiescent)
Sound activated
Sounds
Sound level
Ext. Alarm indicator (AI)
Operating temperature
Storage temperature
Air humidity
Communication protocol
Conductor cross-section on
detector base
Color
Protection category (IEC 60529)
with
Base FDB221 or FDB222
Base attachment FDB291
Base FDB221 and sealing
element FDBZ295
Base attachment humid
FDB293, base attachment wet
FDB295
Standards
Approvals
VdS
LPCB
FM
DNV GL (marine)
System compatibility FDnet
008164_y_en_--
FDS221-R, FDS221-W
DC 12...33 V
Max. 250 µA
3.5 mA
11
2 alarm levels
3 sound levels
80...99 dB(A)
2
-25...+70°C
-30...+75°C
≤95 % rel.
FDnet
According to detector base
~RAL 3000 flame red
~RAL 9010, pure white
Wall mounting with feed line
from below → IP43, otherwise IP40
IP44
IP54
EN 54-3, EN 54-17
G204073
531p
3029351
MEDB00003UV
FS20, AlgoRex, SIGMASYS
Alarm devices in the FDnet
Sounder base FDSB29x
FDSB291
FDSB292
DC 12...33 V
Max. 150 µA
1.2 mA
11
1
2 alarm levels
1 alarm level
2 sound levels
1 sound level
80...88 dB(A)
84 dB(A)
1
-25...+70°C
(observe point detector data)
-30...+75°C
≤95 % rel.
FDnet
Collective
0.2...1.5 mm
~RAL 9010, pure white
IP43
-
-
-
-
EN 54-3
G204062
531u
3029351
MEDB00003UV
FS20, AlgoRex,
SIGMASYS
7
2
-
67 | 152