5.5.3 Technical data
Operating voltage
Operating current (quiescent)
Ext. alarm indicator (AI)
Connection terminals
Operating temperature
Storage temperature
Air humidity
Communication protocol
Color
Protection category (EN 60529 /
IEC 529)
Standards
Design according to EN 54-11
Approvals
–
VdS
System compatibility
–
FDnet
–
C-NET
008164_y_en_--
Manual call point FDM233/234 (direct/indirect alarm activation)
FDM233
~RAL 3000 flame red
EN 54-11, EN 54-17
Type B (indirect activation)
G214019
FS20 / SIGMASYS
FS720 / SIGMASYS
Manual call point
FDM234
DC 12...33 V
Max. 200 µA
2
0.28...1.5 mm
2
-25...+70 °C
-30...+75 °C
≤95 % rel.
FDnet
IP44
Type A (direct activation)
G214020
5
55 | 152