Special detectors
10
Multi-sensor fire detector FDOOT241-A9-Ex
Standards for explosion-hazard areas
Ex approvals
●
EC-type examination certificate
●
IECEx
Approvals
●
VdS
●
DNV GL (marine)
System compatibility
●
FDnet
●
Collective
120 | 152
Ex-related connection
data, intrinsically safe
Line to external alarm
indicator
Symbol
C
0
C
i
I
0
I
i
L
0
L
i
P
0
P
i
U
0
U
i
FDOOT241-A9-Ex
IEC 60079-0, IEC 60079-11
BVS 12 ATEX E 087 X
IECEx BVS 12.0076 X
MEDB00003UK
FS20 / AlgoRex / SIGMASYS
CS11 / FC10 / XC10 / SIGMASYS
U
i
I
i
P
i
L
i
C
i
U
0
I
0
P
0
L
0
C
0
Only for connecting passive, external alarm indicators
with negligibly low inductance and capacitance levels.
Meaning
Maximum external capacitance
Maximum internal capacitance
Maximum output current
Maximum input current
Maximum external inductance
Maximum internal inductance
Maximum output power
Maximum input power
Maximum output voltage
Maximum input voltage
G213106
28 V
100 mA
700 mW
Negligible
0,2 nF
14.2 V
480 mA
195 mW
100 µH
38 nF
008164_y_en_--