Siemens Sinteso FD20 Product Data page 123

Hide thumbs Also See for Sinteso FD20:
Table of Contents

Advertisement

10.7.3 Technical data
Operating voltage
Operating current (quiescent)
Operating temperature
Storage temperature
Air humidity
Communication protocol
Conductor cross section
Color
Protection category (IEC/EN 60529)
With seal DMZ1197-AD
Ex classification
IECEx
Directive 2014/34/EU:
(ATEX directive)
Standards
Standards for explosion-hazard areas
Ex approvals
EC-type examination certificate
IECEx
Approvals
VdS
DNV GL (marine)
System compatibility
FDnet
C-NET
008164_y_en_--
Manual call point FDM223-Ex
FDM223-Ex
DC 13...28 V
200 μA
-25...+70 °C
-35...+75 °C
≤95 % rel.
FDnet-Ex
1...1.5 mm
~RAL 3000 flame red
IP44
IP66
Ex ia IIC T4 Ga, Ta = -35...70 °C
Ex ia IIIB T135 °C Da , Ta = -35...70 °C
II 1 G Ex ia IIC T4 Ga, Ta = -35...70 °C
II 1 D Ex ia IIIB T135 °C Da, Ta = -35...70 °C
EN 54-11 Type B (indirect activation)
EN 60079-0
EN 60079-11
BVS 12 ATEX E 095 X
IECEx BVS 12.0082X
G213107
MEDB00003UM
FS20, AlgoRex, SIGMASYS
FS720
Special detectors
10
2
123 | 152