Input/output modules
9
FDCI222, FDCIO222, FDCIO224
5
FDCIO222
6
FDnet/C-NET
4
1 Fire controls
2 Four relay outputs AC 230 V / 4 A
3 Connections for FDnet detector line
4 3.5 mm MC link jack socket
88 | 152
FDCIO222, FDCIO224 input/output modules
●
Four inputs for potential-free detector contacts
●
Monitoring the input lines for open line and short-circuit with terminating
resistors
●
Inputs can be configured independently for status or alarm messages using the
fire control panel
●
Four outputs with potential-free relay contacts (AC 230 V / 4 A) for fire controls
(FDCIO222) and for the VdS interface in order to activate an extinguisher
triggering device (FDCIO224)
Fields of application:
●
FDCIO222: To activate four independent, potential-free, normally open or
normally closed contacts in order to report technical statuses (e.g., door or fan
control) or to activate an alarm (e.g., sprinkler alarm)
●
For decentralized activation of fire doors, fans and air conditioning systems
●
FDCIO224: For the VdS interface in order to activate an extinguisher triggering
device
1
FDnet/C-NET
3
5 Potential-free detector contacts
6 Four contact inputs
7 VdS interface for extinguishing controls
8 Four relay outputs AC 230 V / 4 A
2
5
FDCIO224
6
FDnet/C-NET
4
7
8
FDnet/C-NET
3
008164_y_en_--