4.4.2.2

X21 outputs for temperature monitoring

Table 4- 8
X21 outputs for temperature monitoring
Terminal
1
2
3
4
Type: Screw terminal 1 (Page 172)
Max. connectable cross-section: 1.5 mm
Note
Internal fans
The internal fans of the HF Choke Module run permanently regardless of the temperature
and whether the pulses are enabled.
Connect the terminals to transfer the temperature signals
The HF line-up does not function without the X21 terminals being connected. Therefore, it is
absolutely necessary that the following terminals are connected with one another to transfer
the temperature signals from the HF Choke Module to the HF Damping Module:
● X21.1 and X21.2 on the HF Choke Module with X21.1 and X21.2 on the HF Damping
Module
● X21.3 and X21.4 on the HF Choke Module with X21.3 and X21.4 on the HF Damping
Module
Use shielded signal cables and connect the cable shields to the supplied shield terminal.
4.4.2.3

X22 fan control for commissioning

Table 4- 9
X22 fan control for commissioning
Terminal
1
2
3
4
Type: Screw terminal 1 (Page 172)
Max. connectable cross-section: 1.5 mm
High Frequency Drive
System Manual, (SH2), 04/2015, 6SL3097-4AH10-0BP3
Function
Technical data
+ KTY
Temperature HF Choke Module analog:
KTY84-1C130 temperature sensor
- KTY
+ Temp switch
Temperature monitoring for the HF Choke Module using the
integrated bimetallic switch
- Temp switch
2
Function
n.c.
n.c.
Disable FAN
Disable FAN
2
Technical data
Using a jumper, the fans can be deactivated for
commissioning.