Items To Check Before The Test Run; Test Run Using The Remote Controller - Panasonic S-200PE2E5 Technical Data & Service Manual

Dc inverter
Table of Contents

Advertisement

2-4. Items to Check Before the Test Run

(1) Turn the remote power switch ON at least 12 hours in advance in order to energize the crankcase heater.
(2) Fully open the closed valves on the liquid-tube and gas-tube sides.

2-5. Test Run Using the Remote Controller

CZ-RTC5A (High-spec wired remote controller)
(1)
Keep pressing the
simultaneously for 4 or more seconds.
The "Maintenance func" screen appears on the LCD display.
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4.Test run
Sel.
Page [
(2)
Press the
or
If you wish to see the next screen instantly, press the
or
button.
Select "4. Test run" on the LCD display and press the
button.
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4.Test run
Sel.
Page [
Change the display from OFF to ON by pressing the
or
button. Then press the
Test run
Test run
Change
[
CZ-RTC4 (Timer remote controller)
(1)
Press the remote controller
Then press the
"
" appears on the LCD display while the test run is in progress.
The temperature cannot be adjusted when in Test Run mode.
(This mode places a heavy load on the machines.
Therefore use it only when performing the test run.)
(2)
The test run can be performed using the HEAT, COOL, or FAN
operation modes.
N OTE
The outdoor units will not operate for approximately 3 minutes after the
power is turned ON and after operation is stopped.
(3)
If correct operation is not possible, a code is displayed on the remote
controller LCD display.
(See the section "7. Self-Diagnostic Function Table and Contents of
Alarm Display" and correct the problem.)
(4)
After the test run is completed, press the
Check that "
" disappears from the LCD display.
(To prevent continuous test runs, this remote controller includes a timer
function that cancels the test run after 60 minutes.)
* If the test run is performed using the wired remote controller, operation
is possible even if the cassette-type ceiling panel has not been
installed. ("P09" display does not occur.)
,
and
buttons
20:30 (THU)
] Confirm
button to see each menu.
20:30 (THU)
] Confirm
button.
20:30 (THU)
ON
] Confirm
button for 4 seconds or longer.
button.
button again.
[
]
START
(3)
Press the
button. "TEST" will be displayed on the
LCD display.
TEST
[
]
START
(4)
Press the
button. Test run will be started.
Test run setting mode screen appears on the LCD
display.
TEST
MODE
COOL
(1)
2-3
20:30 (THU)
CZ-RTC5A
20:30 (THU)
20:30 (THU)
(1)
(4)
CZ-RTC4
2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

U-200pe2e8aU-250pe2e8aS-250pe2e5

Table of Contents