Panasonic S-200PE2E5 Technical Data & Service Manual page 46

Dc inverter
Table of Contents

Advertisement

1
9-6. External Static Pressure Setting
Choose one of the methods (selection of "a", "b", "c" within the range of dotted line as shown in the flowchart below)
and make settings.
a. No setting changes:
When using as it is factory preset at shipment.
(If resetting after external static pressure setting once, it might be different from factory preset.)
b. Manual setting (on PCB):
This is static pressure setting excepting factory preset at shipment. Dip switch select method.
c. Manual setting (by timer remote controller):
Static pressure setting excepting factory preset at shipment.
Flow of External Static Pressure
Start of external static pressure setting
Setting of shipment : line 5
and installed at the setting line
at shipment on PQ line drawing?
Selection methods
of external static
pressure setting
a. No setting changes
NOTE
(1) Refer to Table 1-4, 1-5 and Fig. 1-18 for details on the relationship between the value of item code "5d" and the
external static pressure.
(2) When set in group control (connecting multiple indoor units with one timer remote controller), set each indoor
unit to item code "5d".
When amending the setting after selecting [ b. Manual setting] (due to airflow path changes, etc.), it is
necessary to cancel [b. Manual setting] (switching OFF positions).
When [b. Manual setting] has not been cancelled, [c. Manual setting] will be activated if selected, but [b. Manual
setting] takes precedence when the power is switched back on after power outages, etc.
CAUTION
Is it designed
See the section 9-6-4.
Yes
b. Manual setting
Setting switches of TP6 or
TP3 or TP1
Refer to section "9-6-1. How to
set on PC Board".
Completion of external static pressure setting
Make sure the external static pressure is in a range of specifications.
Then proceed the external static pressure setting.
Improper settings can cause noise, a shortage of airflow volume and water
leakage.
Refer to Fig. 1-18 for the external static pressure setting range.
Be sure to set the [External Static Pressure Setting] once again after amending
the airflow path for the duct or air outlet after setting the external static pressure.
No
No
(Setting on PCB)
1-40
Operating by
timer remote
controller
Yes
c. Manual setting
Item code 5d : Setting 1, 3, 6
(*Note 1) (*Note 2)
Refer to section 9-6-2. or 9-6-3.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

U-200pe2e8aU-250pe2e8aS-250pe2e5

Table of Contents