Display During Auto Address Setting
On the surface of outdoor unit control P.C. board
1
2
LED
* Do not short circuit the A.ADD pin again during auto address setting.
LEDs 1 and 2 go out and address setting is interrupted.
* When auto address setting is normally completed, both LEDs 1 and 2 go out.
Blinks alternately
In other cases, correct settings referring to the following table and perform auto address setting again.
Contents of LEDs 1 and 2 on outdoor unit control P.C. board
: Illuminating
: Blinking
: Go out
LED 1
LED
2
After turned ON power (not during auto address setting), it is entirely impossible to communicate with the
indoor unit in the system.
After turned ON power (not during auto address setting), although the indoor units more than 1 unit in the
system are recognized, there are inconsistencies between the number of indoor units and setting number of
indoor units.
Under auto address setting
Alternately
Auto address setting completed
There are inconsistencies between the number of indoor units and setting number of indoor units.
(at the time of auto address setting)
Simultaneously
Alarm display
Alternating
After LED1 blinks M times, LED2 blinks N times.
This will be repeated.
For example:
(
: Blink)
Connect the outdoor unit maintenance remote controller to the RC plug (3P, BLU) on outdoor main unit control
P.C. board and make confirmation.
Display of remote controller
C
- Z
R
T
C
5A
Auto address
Assigning
Cancel
Request concerning recording the indoor/outdoor unit combination Nos.
After auto address setting has been completed, be sure to record them for future reference.
List the outdoor main unit system address and the addresses of the indoor units in that system in an easily visible location (next
to the nameplate), using a permanent marking pen or similar means that cannot be abraded easily.
Example: (Outdoor) 1 - (Indoor) 1-1, 1-2, 1-3...
These numbers are necessary for later maintenance. Please be sure to indicate them.
Number of blinks
2
3
M
4
5
6
After LED1 blinks twice, LED2 blinks 16 times. This will be repeated.
The alarm shows "P16".
1
(Outdoor) 2 - (Indoor) 2-1, 2-2, 2-3...
C
ontents of display
Type of alarm
Alarm P
Alarm H
N = number of alarm No.
Alarm E
Alarm F
Alarm L
C
- Z
R
T
C
4
2-9
Blinking "
" indicator
2