6. REFRIGERANT INSTALLATION

1. Precautions during refrigerant installation.
Use clean pipes with no dust inside.
The pipe may corrode with the presence of fl uorine dust which will adversely affect the refrigerant piping system due to
deterioration of the refrigerant oil, etc.
This unit is specifi cally for R410A. Ensure to adhere to the following
items and install accordingly:
• Use pipe cutters and fl aring tools which are specially designed for
use with R410A.
• When connecting with fl aring tools, coat the fl are section with ether-
based oil.
• Ensure to use fl are nuts supplied with the unit when connecting this
unit.
• Only for storing or for open pipes.
• Set the lower limit of the allowable pipe length to 5m.
If the pipe is shorter than 5m, the refrigerant may become overfi lled
and a problem such as abnormal high pressure could occur.
• Carefully handle the liquid refrigerant, as it may cause a frostbite.
• Do not release refrigerants during the piping works for installing,
re-installing and repairing refrigeration parts.
2. The local pipes can protrude from any four directions.
Make holes in the pipe panel for the pipes to penetrate it and lay the
pipes accordingly.
• It is recommended to apply additional substance to the cut area for
anti-rust protection.
Ensure to install pipe panels to prevent rain water from getting into
the unit.
Close the gap at the pipe connected area with putty or heat insulator
(locally supplied).
• If an insect or small animal enters the outdoor unit, there is the risk
of shorting in the product electronic casing.
[Remove the front panel]
(1) Remove the 2 mounting screws.
(2) Slide the front panel using your hands downwards to release the
pawls.
Then remove by pulling the panel towards you.
Specifi cation for pipe connecting indoor unit to outdoor unit.
M
a
i x
m
u
m
p
p i
e
e l
Height difference
Piping Connections
M
o
d
l e
n
a
m
e
n
g
h t
Outdoor located higher installation
Outdoor located lower installation
L
q i
u
d i
s
d i
e
G
a
s
s
d i
e
For indoor unit refrigerant piping installation, refer to the installation
instruction manual that comes with that indoor unit.
Do not reuse existing piping, install new piping.
Mounting
screws for the
front panel
Piping
U
2 -
0
0
P
E
2
E
8
A
1
2
0
m
30m
30m
ø
9
5 .
2
ø
2
5
4 .
1-30
Front panel
Front
direction
Downward
Front piping panel
direction
insulator (locally
Prevention measures to avoid small
animals from entering
U
2 -
5
0
P
E
2
E
8
A
1
2
0
m
30m
30m
ø
1
2
7 .
ø
2
5
4 .
Rear
direction
Rear piping
panel
Sideways
direction
Putty or heat
supplied)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

U-200pe2e8aU-250pe2e8aS-250pe2e5

Table of Contents