Panasonic S-200PE2E5 Technical Data & Service Manual page 27

Dc inverter
Table of Contents

Advertisement

CAUTION
(1) When linking the outdoor units in a network, disconnect the terminal extended from the short plug from
all outdoor units except any one of the outdoor units.
(When shipping: In shorted condition.)
For a system without link (no wiring connection between outdoor units), do not remove the short plug.
(2) Do not install the inter-unit control wiring in a way that forms a loop. (Fig. 1-1)
Outdoor unit
Indoor unit
(3) Do not install inter-unit control wiring such as star branch wiring. Star branch wiring causes mis-address
setting. (Fig. 1-2)
(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer.
Central Controller
(5) Use shielded wires for inter-unit control wiring (c) and
ground the shield on both sides, otherwise misoperation
from noise may occur. (Fig. 1-4)
Connect wiring as shown in Section "Wiring System
Diagrams".
(6)
Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 5
or 3 *1.5 mm
flexible cord. Type designation 60245 IEC 57 (H05RN-F, GP85PCP etc.) or heavier cord.
2
Use the standard power supply cables for Europe (such as H05RN-F or H07RN-F which conform to
CENELEC (HAR) rating specifications) or use the cables based on IEC standard. (60245 IEC57, 60245
IEC66)
Loose wiring may cause the terminal to overheat or result in unit malfunction.
WARNING
A fire hazard may also occur. Therefore, ensure that all wiring is tightly connected.
When connecting each power wire to the terminal, follow the instructions on "How to connect wiring to the terminal" and
fasten the wire securely with the terminal screw.
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
NO
Indoor unit
Outdoor unit
: Branch point
Outdoor unit
Outdoor unit
Outdoor unit
Prohibited
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Branch point
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
SG
1-21
Prohibited
Indoor unit
Fig. 1-1
Fig. 1-2
Indoor unit
Indoor unit
Indoor unit
Fig. 1-3
Shielded wire
SG
Fig. 1-4
1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

U-200pe2e8aU-250pe2e8aS-250pe2e5

Table of Contents