Soft Start Period
Fast Running Period
15 seconds
Factory default setting for the Fast Running Period is 15 seconds. Please
consider the below calculation example. When the Soft Start Period is set at 3
seconds and the Total Run Time is 23 seconds, the Fast Running Period has to
be adjusted to 15 seconds in order to meet the Soft Stop Period of 5 seconds.
Adjust in the
Menu Pb
3
seconds
1.
The Fast Running Period can be adjusted by pressing the INC or DEC
buttons.
2.
Press the button FUNC in order to store the setting.
The display shows Pd.
3.
Press the button FUNC once more in order to quit the menu and to save the
setting.
The display shows "– –".
Programming
+
Fast Running Period
=
Total Run Time
=
23 seconds
Adjust in the
Menu PC
15
seconds
+
Soft Stop Period
–
Soft Start Period
–
3 seconds
This will result to
a Soft Stop Period
of 5 seconds
24
=
Total Run Time
–
Soft Stop Period
–
5 seconds
This will result to
a Total Run Time
of 23 seconds