Boiler Jacket - Buderus Logano plus SB615 Installation And Servicing Instructions

Condensing boiler for operation with fanassisted gas burner
Table of Contents

Advertisement

7
Installation
USER NOTE
Follow the burner manufacturer's instruc-
tions when fitting the burner.
The appropriate burner plate must be
used/modified according to the make/model
of the burner.
The gap between the burner tube and the
thermal insulation must be sealed by the in-
staller (Fig. 18).
Refractory is supplied with the boiler. It must
be cut to the right size to fit.
7.4

Boiler jacket

USER NOTE
On the SB615/400 and larger boilers, the
second top panel section has a cutout
(Fig. 19, Item 1); the rear sections are iden-
tical and are positioned with the flanged
edge to the front.
SB615/145 to 400 boilers
4 top panel sections
SB615/510 to 640 boilers
5 top panel sections
Position top panel sections loosely on side panels at
each side.
18
Fig. 18
Item 1: Gap between burner tube and insulation
Fig. 19
Item 1: Cutout on SB615/400 and up.
Logano plus SB615 - Technical specifications are subject to change without prior notice.
7-5/16"
(185)
Sealing the gap between burner and insulation.
Refractory may have to be cut to size depending on
burner make and model.
1
Fitting boiler top panel sections – general principle
1