Commissioning the heating system
6.8

Manual reset high limit (STB)

The manual reset high limit interrupts the power supply if the maximum
permissible flow temperature is exceeded.
To enable a boiler reset and re-starting, the fault must be removed and
the system temperature must have fallen below the limit.
▶ Check the function of the manual reset high limit
( controls maintenance instructions).
6.9

Installing the burner door jacket

▶ Position the burner door panel on the hooks on the boiler casing.
▶ Secure the burner door panel with the two screws at the sides.
DANGER: Risk of fatal injury from electric shock.
▶ Only operate the boiler with the burner hood/door
panel fitted.
▶ The Logano G115 WS must be fitted with a burner that has an
operating range that matches the specifications of the Logano G115
WS.
CAUTION: Risk of system damage from use of incorrect
fuel.
▶ Only use burners which meet the technical
requirements of the Logano G115 WS ( Chapter
2.7, page 8).
▶ Mount the selected burner to the hole circle in the burner door.
▶ Connect burner cable to burner. ( Installation instructions of
burner).
Fig. 34 Installing the burner door jacket
32
7 720 615 225-03.1RS
Logano G115 WS US/CA – 6 720 813 418 (2019/09)