BARTEC BENKE HYGROPHIL H 4230-12 Ex Zone II Operating Instructions Manual page 105

Table of Contents

Advertisement

7
6
ON
Errortimeout Control bit
DaAdr $42: HeatingContolStatus
Format: Record
End;
Statuschar:
5
4
HoseError
for control
ON:
1 = Controller is switched on and working
0 = Controller off
Errortimeout: 1 = Error-tolerant period expired
0 = Equipment in normal operation
Control bit for control (function display for heating)
1 = Heating is currently activated
0 = Heating is currently not activated
HoseError:
1 = Fault (short circuit, interruption) on the hose heating
0 = Hose heating OK
D-limit:
1 = D component limit exceeded
0 = D component OK
PID-active:
1 = PID controller active, i.e. xp range reached
0 = P control
I-limit:
1 = I component limit exceeded
0 = I component OK
ON time:
Time in ms during which the hose heating is switched on.
OFF time.
Time in ms during which the hose heating is switched off.
DaAdr $46: ErrorTime
Format: Integer
Before you can write this variable you must first change to standby mode.
Switch-off time (0...3599) after an error occurs that makes regular meas-
urement operation impossible.
No switch-off at 9999s.
Default = 1200s
DaAdr $47: HT without comp
Format: Float
HT with or without compensation.
HT measured value in °C, measurement range: 0...100 °C.
Operating Instructions HYGROPHIL® H 4230-12 BA 060207
Statuschar: Char;
dummy;
Char;
ON time;
Integer;
OFF time;
Integer;
3
2
Free
D limit
PROFIBUS
99
1
0
PID active
I limit