Mitsubishi Electric QJ71MT91 User Manual page 182

Modbus/tcp interface module
Table of Contents

Advertisement

9
PROGRAMMING
Device Name
Input
QJ71MT91
input/output
Output
External input (command)
External output
Data register
Internal relay
9 - 16
(3)
Devices used in program
Device
X0
Module READY
X1
Basic parameter setting, normally completed
X2
Basic parameter setting, error completed
X3
Basic parameter setting existence
X4
Automatic communication parameter setting, normally completed
X5
Automatic communication parameter setting, error completed
X6
Automatic communication operation status
X8
MODBUS device assignment parameter setting, normally completed
X9
MODBUS device assignment parameter setting, error completed
Y1
Basic parameter setting request
Automatic communication parameter setting request/automatic
Y4
communication start request
Y8
MODBUS device assignment parameter setting request
X20
Parameter setting command
Y40
Automatic communication parameter 1 communication error
Y41
Automatic communication parameter 2 communication error
D4000 to D4003 Automatic communication operation status storage area (parameter 1 to 64)
D4008 to D4071 Automatic communication error code storage area (parameter 1 to 64)
D4092 to D4095
For auto refresh
D4096 to D4159
D5000 to D5099
D9001
Basic parameter error code acquisition
D9002
Automatic communication parameter error code acquisition
D9003
Automatic communication parameter setting result acquisition
D9004
MODBUS device assignment parameter error code acquisition
MODBUS device
D9005
assignment
parameter setting
D9006
result acquisition
Automatic
D9100
communication error
D9101
code
M1
For automatic communication parameter setting command
M2
For MODBUS device assignment parameter setting command
Automatic
M401
communication
M402
normal
Application
Automatic communication operation status storage
area (parameter 1 to 64)
Automatic communication function buffer input area
Automatic communication function buffer output area
Error, device type
Error, assigned group No.
Automatic communication parameter 1
Automatic communication parameter 2
For automatic communication parameter 1
For automatic communication parameter 2
MELSEC-Q
(Continued on next page)
9 - 16