4.10.3 Resetting Latched Events

Note: Password access is required.
Acknowledged latched events can be reset in three ways:
5) By logging in and pressing the
warnings, provided that the event has cleared. It will also reset any latched relay outputs.
6) By logging in and selecting Menu>Maintenance>Reset Alarms/Faults. This will reset all latched
events, provided that the input signal has returned to Normal / within tolerance.
7) By holding the Remote reset switch for >3 seconds. TPPLW has the option of adding a remote
acknowledge / reset switch up to 500 m away from the Controller. The remote reset switch does not
require a login so a key-lockable switch should be used to prevent unauthorised access.
Note: Alarm/Event reset will only work when the triggering event situation has cleared (e.g. gas alarm, fault
situation etc.). In case of mV sensor's over-range alarm, user shall not reset the over-range alarm until it is
verified that the flammable gas has cleared.
Note: The fault events are always latched except the communication fault.

4.11 Inhibiting Channels

Note: Service or higher access level is required.

4.11.1 To Inhibit Input Channels:

8) Log in as Administrator or Service
9) Touch a channel, then touch the inhibit icon:
10) Or use a Remote Inhibit input (key-locking) switch.
11) Or set input channel gas sensor to inhibit mode so that Touchpoint Plus will receive respective current.

4.11.2 To Clear Inhibits:

12) Log in as Administrator or Service
13) Touch an inhibited channel, then touch the inhibit icon:
14) Or use a Remote Inhibit input (key-unlocking) switch
15) Or Touchpoint Plus's channel in inhibit mode will automatically clear an inhibit when input channel gas
sensor's inhibit is cleared
Note: An auto-inhibit cannot be cleared manually. Auto-inhibits may occur during calibration or warm-up,
when a transmitter is signalling Inhibit, or when an Inhibit delay time is running.
User Guide
button for >3 seconds. This will reset ALL latched alarms, faults and
and then touch [Yes]
32
Touchpoint Plus Wireless
and then touch [Yes]