2.8.2 How to attach probes to the bottom of the tank

If the liquid is agitated or turbulent, you can attach the probe to the bottom of the tank. The
procedure to attach the probe depends on the type of probe used.
For more data, refer to the Handbook.

2.8.3 Standpipes

Use a standpipe if:
• There is highly conductive foam in the tank.
• The liquid is very turbulent or agitated.
• There are too many other objects in the tank.
• The device is measuring a liquid (petro-chemicals) in a tank with a floating roof.
For more data, refer to the Handbook.
Figure 2-15: Basic installation recommendations for standpipes (stilling wells and bypass chambers)
1 Stilling well
2 Bypass chamber
3 Air circulation hole
4 Level of the liquid
INFORMATION!
Standpipes are not necessary for devices with coaxial probes. But if there is a sudden change in
diameter in the standpipe, we recommend that you install a device with a coaxial probe.

2.9 Installation recommendations for solids

2.9.1 Nozzles on conical silos

We recommend that you prepare the installation when the silo is empty.
03/2014 - 4000049806 - QS OPTIFLEX 1300 R09 en
www.krohne.com