5.3.1

View: State, main device

Screen: State of main device
Figure 5-23
Elements
Table 5- 41
Screen area Parameter
PSU8600
Operating state and
information
<Text field>
SITOP PSU8600 Firmware V1.3: Faceplates and Communication Blocks V2.3 for SIMATIC STEP 7 V5.5
Function Manual, 11.2017, A5E37764016-06-76
Description
The operating state displays various colors depending on the state of PSU8600.
The <text field> displays the operating state as plain text.
Text
Power supply system is switched off.
Power supply system was automatically switched
off due to operation under impermissible operating
conditions.
The power supply system can be reactivated
again after automatic shutdown due to an error by
switching the supply voltage off and on.
The power supply system is starting up; all out-
puts are still switched off.
The power supply system is in normal operation.
A phase failure of the supply voltage was detect-
ed. The power supply system can continue normal
operation without restriction for a limited time.
System overload within the permissible overload
profile detected; the power supply system contin-
ues to operate in normal mode.
Blocks of the library
5.3 Explanation of WinCC faceplates
Number
Color
0
White
1
Red
2
Red, flashing
3
White
4
Green
5
Green, flashing
6
Green, flashing
51