Input parameters
Table 5- 35
Parameter
Execute
HW_Ident_Head
Cyclic_IO_OUT_Head_addr
Buffering_In_Param
Structure of UDT_Data_Buffering_V2 data type
Table 5- 36
Parameter
Buffer_disable
Longlife_mode
Charge_ready_threshold
Power_interrupt_enable
Padding
Power_interrupt_deadtime
Power_interrupt_waittime
Power_interrupt_inttime
Input/output parameters
Table 5- 37
Parameter
Data
Output parameters
Table 5- 38
Parameter
Buffering_Out_Param
SITOP PSU8600 Firmware V1.3: Faceplates and Communication Blocks V2.3 for SIMATIC STEP 7 V5.5
Function Manual, 11.2017, A5E37764016-06-76
5.2 Explanation of SIMATIC STEP 7 blocks
Data type
BOOL
WORD
WORD
UDT_Data_Buffering_V2 UDT for buffering input parameters
Data type
BYTE
BYTE
WORD
BYTE
BYTE
WORD
DWORD
WORD
Data type
UDT_PSU8600_Data_V2
Data type
UDT_Buffering_OUT_V2
Blocks of the library
Description
On the rising edge (0 > 1), data at the
inputs of the block is written to the PSU.
Start address of the entire main module.
Output address of main module IO data
submodule.
Description
Enables or disables buffer mode
(0 = no, Any other value = yes)
Long life mode
(0 = no, Any other value = yes)
Charge ready threshold (10 to 90%,)
Power interrupt enable
(0 = no, Any other value = yes)
Unused
Power interrupt dead time (0 to 60000 ms)
Power interrupt wait time (0 to 300000 ms)
Power interrupt interrupt time
(0 to 60000 ms)
Description
Data block for global data exchange. DB
must follow the UDT structure.
Description
UDT for buffering output parameters
45