Next NI2400 User Manual page 50

24-channel ethernet data logger with embedded web server
Table of Contents

Advertisement

4
DATALOGGER
NI2400
BASE_VIRT+1268 -
MSB-LSB Temperature Script5 Ch16
BASE_VIRT+1269
BASE_VIRT+1270 -
Timestamp acquisition Script5 Ch16
BASE_VIRT+1278
BASE_VIRT+1279
Flags Script5 Ch16
SENSORS BASE ADDRESS
Following formulas will show how to get every connected sensor's base address.
Local Sensors (Analog)
BASE_ANALOG = 0
Channel_ADDRESS = (Channel-1)*16 + BASE_ANALOG
8CH Channel = [1;8]
24CH Channel = [1;24]
Digital Sensors (Smart Modbus)
8CH
24CH
BASE_DIG
128
384
Channel_ADDRESS = (Channel-1)*16 + BASE_DIG
Channel = [1;254]
Multiplexer Sensors
8 CH
24 CH
BASE_MUX
4224
4480
Channel_ADDRESS = ((Address-1)*32*16)+((Channel-1)*16)+BASE_MUX
Address = [1;16], Channel = [1;24]
Digital Inputs
8 CH
24 CH
BASE_DIN
12416
12672
www.ruggedaq.com
4
Channel_ADDRESS = ((Channel-1)*16) + BASE_DIN
Script5 - Ch16
Channel = [1;2]
Script5 - Ch16
Virtual Channels
Script5 - Ch16
BASE_VIRT
Channel_ADDRESS = ((Script-1)*16*16)+((Channel-1)*16)+BASE_VIRT
Script = [1;5], Channel = [1;16]
Event Log Registers
This register set handles Event Log status.
For every log, timestamp, and code is exposed.
This register set starts at Modbus address 0x3800 (14336 DEC).
STATUS REGISTERS
This register exposes information about the datalogger. Base Address for this register is
098
DATALOGGER
NI2400
8 CH
24 CH
12448
12704
REGISTER
DESCRIPTION
14336 - 14344
Timestamp Event n
14346
Event Code n
14347-14410
Event String n
14411 – 14419
Timestamp Event n-1
14421
Event Code n -1
14422-14485
Event String n -1
...
...
...
...
...
...
15816 – 15824
Timestamp Event n -19
15826
Event Code n -19
15827-15890
Event String n -19
www.ruggedaq.com
Event n
Event n
Event n
Event n-1
Event n-1
Event n-1
...
...
...
Event n-19
Event n-19
Event n-19
099