Installing Or Replacing Power Supplies; Installing Or Replacing A 3-Kw Ac Power Supply - Cisco Nexus 9516 Hardware Installation Manual

Nx-os mode
Hide thumbs Also See for Nexus 9516:
Table of Contents

Advertisement

Installing or Replacing Power Supplies

e) Screw in the four captive screws to secure the fan tray to the chassis. Tighten the screws to 8 in-lb (0.9 N·m) of torque.
f) Verify that the fan tray and fabric module STATUS LEDs (on the fan tray) turn on and become green.

Installing or Replacing Power Supplies

The number of 3-kW and 3.15-kW power supplies that you install depends on the power requirements of the
switch. It also depends on the power mode that you are using. To determine the power requirements of the
switch, see the
If you are using only one power source for the combined mode or n+1 redundancy mode, you can install the
power supplies in any of the power supply slots on the chassis. If you are using two power sources for the
n+n redundancy mode, you must connect the power supplies in slots 1 through 5 to one power source and the
power supplies in slots 6 through 10 to the other power source. With n+n redundancy mode, divide the power
supplies evenly between the first half of the slots and the last half of the slots. The amount of redundant power
for the switch equals the amount of available power for the switch.
Warning
Statement 1034—Backplane Voltage
Hazardous voltage or energy is present on the backplane when the system is operating. Use caution when
servicing.
Warning
Statement 1029—Blank Faceplates and Cover Panels
Blank faceplates and cover panels serve three important functions: they prevent exposure to hazardous voltages
and currents inside the chassis; they contain electromagnetic interference (EMI) that might disrupt other
equipment; and they direct the flow of cooling air through the chassis. Do not operate the system unless all
cards, faceplates, front covers, and rear covers are in place.
You can install or replace any of the following Cisco Nexus 9500 Series power supplies in this switch:
• 3-kW AC Power Supply
• 3-kW Universal AC/DC Power Supply
• 3.15-kW Dual Input Universal AC/DC Power Supply
• 3-kW DC Power Supply

Installing or Replacing a 3-kW AC Power Supply

Before you begin
• The AC power source must be installed within reach of the power cables.
• The AC power source meets the power specifications that the switch requires.
Cisco Nexus 9516 NX-OS Mode Switch Hardware Installation Guide
82
Power Requirements for Switch Modules
Replacing or Installing Modules, Fan Trays, and Power Supplies
section.

Advertisement

Table of Contents
loading

Table of Contents