Preparing the Site
Component
32-port 100-Gigabit Ethernet QSFP28 line card (N9K-X9732C-EX)
32-port 100-Gigabit Ethernet QSFP28 line card (N9K-X9732C-FX)
Fan Trays (N9K-C9516-FAN)
For example, to determine the maximum amount of power that your fully loaded switch consumes, add the maximum
power consumption of two supervisor A modules (2 x 80 W = 160 W), two system controllers (2 x 25 W = 50 W), 16
48-port 10GBASE-T line cards (16 x 540 W = 8640 W), six fabric modules (6 x 504 W = 3024 W), and three fan trays
(3 x 451 W = 1353 W). The total is 13,227 W.
Step 2
Determine the number of power supplies required to power the modules that are installed in the switch by dividing the
module power requirement amount (see Step 1) by the output wattage (3000 W) of the power supplies installed in the
switch. Round up the fractional result to the nearest ones digit.
For example, if you are installing a switch with maximum consumption of 13,224 W, you need five power supplies
(13,224 W / 3000 W = 4.41 [rounded up to three power supplies]) to operate the switch and its modules.
Step 3
Determine the amount of power that is required from a power source.
The power supplies are rated to have at least 91-percent efficiency.
• To determine the input power (Watts) from the power source to the power supplies, divide the output power of each
power supply (3000 W) by the efficiency of the power supply (0.91) and then multiply the result by the number of
power supplies required to power the switch. For example, if the switch uses 5 power supplies, you can calculate
the amount of power that is required from the power source as follows:
3000 W output / 0.91 efficiency X 5 power supplies = 16,485 W
• To determine the number of Amps (A) that are required to power the switch, divide the maximum Watts that is
required for by the voltage that is used as shown in the following examples:
• For 16,485 A at 200-volts AC (VAC), use the following formula:
(16,485 W)/(200 VAC) = 82.5 A
• For 16,485 A at 277-volts AC (VAC), use the following formula:
(16,485 W)/(277 VAC) = 59.5 A
• For 16,48516,500 A at 380-volts DC (VDC), use the following formula:
(16,485 W)/(380 VDC) = 43.4 A
• To determine the required BTUs, multiply the Watts that is required for the power source by 3.41214163.
For example, for 16,485 W, use the following formula:
(16,485 W) X (3.41214163 BTU) = 56,249
To size the circuit breaker for the required amperage, you must also divide the required amperage by the percentage. For
example, if the switch requires an input amperage of 82.5 A and you are able to use up to 80 percent of the capacity of
a circuit breaker, you use the following formula to calculate the minimum amperage that is required of the circuit breaker:
(82.5 A)/ (80% or 0.80) = 103.1 amps
Cisco Nexus 9516 NX-OS Mode Switch Hardware Installation Guide
Planning for Power Requirements
Typical
Maximum
430 W
720 W
840 W
330 W