Fault finding and diagnosis
Fault
Display text
code
Internal error
b7
Internal error
F0
EH
Internal error
F1
Internal error
F0
Internal error
F1
Internal error
F0
Internal error
F0
Internal error
F0
Internal error
A8
CC
Table 49
68
Cause
code
Description
257
Control box or the HCM is defective.
258
Control box or the HCM is defective.
258
259
Control box or the HCM is defective.
262
Control box or the HCM is defective.
263
Control box or the HCM is defective.
272
Control box or the HCM is defective.
280
Control box is defective.
290
Control box is defective, (Analogue /
Digital converter reference error).
328
Internal error (Mains voltage / frequency
may be inconsistent)
235
Incompatible HCM software version
356
Low mains voltage, (the voltage may be
interrupted or inconsistent).
360
HCM invalid
361
HCM invalid
363
Ionisation measuring fault
356
Low mains voltage, (the voltage may be
interrupted or inconsistent).
800
Outdoor sensor defect (available when
accessary outdoor sensor is connected)
Possible solution/check
▶ Check:
– HCM is inserted properly.
– Connections of the control box.
▶ Contact technical helpline.
▶ Check:
– HCM is inserted properly.
– Connections of the control box.
▶ Contact technical helpline.
▶ Check:
– HCM is inserted properly.
– Connections of the control box.
▶ Contact technical helpline.
▶ Check:
– HCM is inserted properly.
– Connections of the control box.
▶ Contact technical helpline.
▶ Check:
– HCM is inserted properly.
– Connections of the control box.
▶ Contact technical helpline.
▶ Check:
– HCM is inserted properly.
– Replace HCM if necessary.
– Connections of the control box.
▶ Replace control box if necessary.
▶ Check:
– HCM is inserted properly.
– Connections of the control box.
▶ Replace control box if necessary.
▶ Check:
– HCM is inserted properly.
– Connections of the burner control.
▶ Replace burner control if necessary.
▶ Check the voltage and frequency.
Revised HCM software requires latest version of control
box to operate correctly
▶ Replace the control box with the latest software.
On the barcode label of the burner control the software
version is indicated.
▶ Check mains voltage.
The inserted HCM does not correspond with the control
box. HCM must be within the same appliance type.
▶ Check the correct HCM is fitted.
– HCM identification number found in Technical data
table.
The inserted HCM does not correspond with the control
box or HMI type.
▶ Contact technical helpline.
▶ Check earth harness's and connections
▶ Check mains voltage.
▶ Check:
– Sensor harness and connector.
– Operation, replace if necessary.
Greenstar i System
ErP
- 6 720 806 945 (2015/07)