How to Install
3.3 Electrical Installation
3.3.1 Cables General
CAUTION
Cables general:
Always comply with national and local regulations on cable cross-sections.
Frame
200-240 V
380-500 V
size
[kW]
[kW]
B1
5.5-7.5
11-15
B2
11
18.5-22
B3
5.5-7.5
11-15
B4
11-15
18.5-30
C3
18.5-22
-
Table 3.6 Tightening Torque
3.3.2 Removal of Knockouts for Extra Cables
•
Remove cable entry from the frequency converter (avoiding foreign parts in the frequency converter when
removing knockouts)
•
Support cable entry around the knockout that should be removed
•
The knockout can now be removed with a strong mandrel and a hammer
•
Remove burrs from the hole
•
Mount cable entry on frequency converter
MG34M422
Operating Instructions
525-690 V
Cable for
[kW]
Mains, motor cables
15
Relay
Ground
Mains
Motor cables
18.5-22
Relay
Ground
Mains, motor cables
15
Relay
Ground
Mains, motor cables
18.5-22
Relay
Ground
Mains, motor cables
-
Relay
Ground
Danfoss A/S © Rev. 2013-07-03 All rights reserved.
Tightening torque
[Nm]
1.8
0.5-0.6
2-3
4.5
4.5
0.5-0.6
2-3
1.8
0.5-0.6
2-3
4.5
0.5-0.6
2-3
10
0.5-0.6
2-3
17
3
3