How to Program
•
parameter 8-37 Max Inter-Char Delay
•
parameter 14-50 RFI 1
•
parameter 15-00 Operating hours
•
parameter 15-01 Running Hours
•
parameter 15-02 kWh Counter
•
parameter 15-03 Power-ups
•
parameter 15-04 Over Temps
•
parameter 15-05 Over Volts
•
parameter 15-20 Historic Log: Event
•
parameter 15-21 Historic Log: Value
•
parameter 15-22 Historic Log: Time
•
parameter 15-30 Fault Log: Error Code
•
parameter 15-31 Fault Log: Value
•
parameter 15-32 Fault Log: Time
Manual initialization
1.
Disconnect from mains and wait until the display
turns off.
2.
Press [Status] - [Main Menu] - [OK] at the same
time while power up for LCP 102, Graphical
Display.
3.
Release the keys after 5 s.
4.
The frequency converter is now programmed
according to default settings.
This procedure initializes all except:
•
parameter 15-00 Operating hours
•
parameter 15-03 Power-ups
•
parameter 15-04 Over Temps
•
parameter 15-05 Over Volts
5.2.7 Data Transfer from LCP to Frequency
Converter
NOTICE!
Stop the motor compressor before performing this
operation.
1.
Go to parameter 0-50 LCP Copy.
2.
Press [OK].
3.
Select [2] All from LCP.
4.
Press [OK] again.
MG34M422
Operating Instructions
The parameter settings stored in the LCP are now
transferred to the frequency converter indicated by the
progress bar. When 100% is reached, press [OK].
Danfoss A/S © Rev. 2013-07-03 All rights reserved.
5
5
43