Fault Mode - Write Word 0; Add-On Filter Selections - Write Word 0; Reference Junction Selection - Write Word 0 - Allen-Bradley FLEX Ex 1797-IRT8 Installation Instructions Manual

Thermocouple/rtd input module
Table of Contents

Advertisement

16 FLEX Ex Thermocouple/RTD Input Module

Fault Mode - Write Word 0

Bit
06
Fault enable for channels 0...3
07
Fault enable for channels 4...7
0 = disabled
1 = enable wire-off detection

Add-on Filter Selections - Write Word 0

Bit
02
01
0
0
0
0
0
1
0
1
1
0
1
0
1
1
1
1

Reference Junction Selection - Write Word 0

Bits
Reference Junction - used when sensor is set to thermocouple
03...05
and sensor mode is set to internal compensation. Sets a fixed
reference junction to compensate all thermocouple channels.
Bit
Publication
1797-IN004G-EN-P - August 2017
00
Definition
0
Hardware filtering only (default filtering)
1
40 Hz (25 ms)
0
10 Hz (100 ms)
1
4 Hz (250 ms)
0
2 Hz (500 ms)
1
1 Hz (1 s)
0
0.5 Hz (2 s)
1
0.2 Hz (5 s)
05
04
0
0
0
0
0
1
0
1
1
0
1
0
1
1
1
1
03
Reference Junction
0
0 °C
1
20 °C
0
25 °C
1
30 °C
0
40 °C
1
50 °C
0
60 °C
1
70 °C

Hide quick links: