19 Default Setting Values

Label
SEt
Setpoint
HY
Differential
LS
Minimum setpoint
US
Maximum setpoint
ot
Thermostat probe calibration
P2P
Evaporator probe presence
oE
Evaporator probe calibration
P3P
Third probe presence
o3
Third probe calibration
P4P
Fourth probe presence
o4
Fourth probe calibration
odS
Outputs delay at start up
AC
Anti-short cycle delay
rtr
P1-P2 percentage for regulation
CCt
Continuous cycle duration
CCS
Setpoint for continuous cycle
Compressor ON time with faulty
Con
probe
Compressor OFF time with faulty
CoF
probe
CF
Temperature measurement unit
rES
Resolution
Lod
Probe displayed
2
X-REP display
rEd
dLY
Display temperature delay
dtr
P1-P2 percentage for display
tdF
Defrost type
Probe selection for defrost
dFP
termination
Table 19-1- XR75CX Default Setting Values (
26 • XR75CX I&O Manual
Name
2
Only for XR75CX with X-REP output)
Range
LS to US
[0.1 to 25.5°C]
[1 to 255°F]
[-50°C to SET]
[-58°F to SET]
[SET to 110°C]
[SET to 230°F]
[-12 to 12°C]
[-21 to 21°F]
n=not present; Y=pres.
[-12 to 12°C]
[-21 to 21°F]
n=not present; Y=pres.
[-12.0 to 12.0°C]
[-21 to 21°F]
n=not present; Y=pres.
[-12.0 to 12.0°C]
[-21 to 21°F]
0 to 255 min
0 to 50 min
0 to 100 (100=P1, 0=P2)
0.0 to 24h 00min, res. 10min
[-50 to 110.0°C]
[-58 to 230°F]
0 to 255 min
0 to 255 min
°C; °F
in=integer; dE= dec.point
P1; P2
P1; P2; P3; P4; SEt; dtr
0.0 to 20min 00s, res. 10s
1 to 99
EL=el. heater; in= hot gas
nP; P1; P2; P3; P4
Value
Level
[-5.0°C]
- - -
[23°F]
[2.0°C]
Pr1
[2°F]
[-50.0°C]
Pr2
[-58°F]
[110.0°C]
Pr2
[230°F]
[0.0°C]
Pr1
[0°F]
Y
Pr1
[0.0°C]
Pr2
[0°F]
n
Pr2
[0.0°C]
Pr2
[0°F]
n
Pr2
[0.0°C]
Pr2
[0°F]
0
Pr2
1
Pr1
100
Pr2
0.0
Pr2
[-5°C]
Pr2
[23°F]
15
Pr2
30
Pr2
[°C] [°F]
Pr2
dE
Pr1
P1
Pr2
P1
Pr2
0.0
Pr2
50
Pr2
EL
Pr1
P2
Pr2
026-1210 Rev 4