Emerson Dixell XR75CX Series Installation And Operation Manual page 33

Digital controller for medium-low temperature refrigeration applications
Hide thumbs Also See for Dixell XR75CX Series:
Table of Contents

Advertisement

Label
dtE
Defrost termination temperature
idF
Interval between defrost cycles
MdF
(Maximum) length for defrost
dSd
Start defrost delay
dFd
Displaying during defrost
dAd
MAX display delay after defrost
Fdt
Draining time
dPo
First defrost after start-up
dAF
Defrost delay after fast freezing
FnC
Fan operating mode
Fnd
Fan delay after defrost
Differential of temperature to force
FCt
fan activation
FSt
Fan stop temperature
Fon
Fan on time with compressor off
FoF
Fan off time with compressor off
FAP
Probe selection for fan management
ACH
Kind of action for auxiliary relay
SAA
Setpoint for auxiliary relay
SHY
Differential for auxiliary relay
ArP
Probe selection for auxiliary relay
Auxiliary relay operating during
Sdd
defrost
ALP
Alarm probe selection
ALC
Temperat. alarms configuration
ALU
MAXIMUM temperature alarm
ALL
Minimum temperature alarm
Differential for temperat. alarm
AFH
recovery
ALd
Temperature alarm delay
dAo
Delay of temperature alarm at start up
Probe for temperat. alarm of
AP2
condenser
AL2
Condenser for low temperat. alarm
Table 19-1- XR75CX Default Setting Values (
MODBUS Termination Blocks
Name
2
Only for XR75CX with X-REP output)
Range
[-50 to 50°C]
[-50 to 122°F]
1 to 120 hours
0 to 255 min
0 to 99 min
rt, it, SEt, DEF
0 to 255 min
0 to 120 min
n=after idF; Y=immed.
0 to 24h 00min, res. 10min
C-n; o-n; C-Y; o-Y
0 to 255 min
[0 to 50°C]
[0 to 90°F]
[-50 to 50°C]
[-58 to 122°F]
0 to 15 min
0 to 15 min
nP; P1; P2; P3; P4
CL; Ht
[-50 to 110°C]
[-58 to 230°F]
[0.1 to 25.5°C]
[1 to 45°F]
nP; P1; P2; P3; P4
n; Y
nP; P1; P2; P3; P4
rE= related to set;
Ab = absolute
[SEt to 110.0°C]
[SEt to 230°F]
[-50°C to SEt]
[-58°F to SEt]
[0.1°C to 25.5°C]
[1°F to 45°F]
0 to 255 min
0 to 24h 00min, res. 10min
nP; P1; P2; P3; P4
[-50 to 110°C]
[-58 to 230°F]
Value
Level
[8°C]
Pr1
[46°F]
6
Pr1
30
Pr1
0
Pr2
it
Pr2
30
Pr2
0
Pr2
n
Pr2
0.0
Pr2
o-n
Pr1
10
Pr1
[10°C]
Pr2
[10°F]
[36°C]
Pr1
[23°F]
0
Pr2
0
Pr2
P2
Pr2
CL
Pr2
[0.0°C]
Pr2
[32°F]
[2.0°C]
Pr2
[2°F]
nP
Pr2
n
Pr2
P1
Pr2
Ab
Pr2
[110°C]
Pr1
[230°F]
[-50.0°C]
Pr1
[-58°F]
[2.0°C]
Pr2
[2°F]
15
Pr2
1.3
Pr2
P4
Pr2
[-40.0°C]
Pr2
[-40°F]
Default Setting Values • 27