3.0
Typical Releasing Applications
3.1
Pre-Action/Agent Release, Single Activation Application
Devices
SLC Loop
Any Detector in Hazard
Zone
Releasing Agent
Addressable Module
Abort Switch
Manual Release Switch
Logic
AND Gate
Both inputs are required.
Logic Path
OR Gate
If either input is activated
release occurs.
NOT Gate
Input is required to be not
activated.
Delay Timer
Use FX-3500RCU
Configurator to set type.
Release commences if the following events occur:
•
a single detector correlated to the Hazard Zone enters alarm
•
the abort switch is not pressed
•
the Manual Release Switch is pressed
•
the delay timer expires
OR
•
the delay timer expires