2.1 General Specifications
2.1.1

Electrical

Input Voltage
Rated Voltage
Rated
Frequency
Allowable
Power
Voltage Drop
Supply
Power
Consumption
In-Rush Current
Voltage Endurance
Insulation Resistance
2.1.2

Environmental

Surrounding Air
Temperature
Storage Temperature
Ambient Humidity
Storage Humidity
Dust
Pollution Degree
Corrosive gas
Atmosphere
(Using height)
2-2
PS-3650A/PS-3651A Series
AC Power Supply Type
(PS3650A-T42/
PS3651A-T42/
PS3650A-T42S/
PS3651A-T42S)
AC100/240V
AC85 to 265V
50/60Hz
1 cycle or less (Voltage drop
interval must be 1s or more.)
PS-3650A Series:110VA or less
PS-3651A Series:95VA or less
AC100V (room temperature):
30A or less
AC240V (room temperature):
50A or less
AC1,500V 20mA for 1 minute
(between charging and FG
terminals)
DC500V 10MΩ(min.) (between charging and FG terminals)
PS-3650A Series
0 to 50°C: without HDD
5 to 50°C: with HDD
(Not condensing, wet bulb temperature: 39°C or less. Wet bulb
temperature with HDD: 29°C or less.)
(Not condensing, wet bulb temperature: 39°C or less.)
3
0.1mg/m
and below (non-conductive levels)
For use in Pollution Degree 2 environment
PS-3650A/PS-3651A Series
DC Power Supply Type
(PS3650A-T42-24V/
PS3651A-T42-24V/
PS3650A-T42S-24V/
PS3651A-T42S-24V)
DC24V
DC19.2 to 28.8V
5ms (max.)
PS-3650A Series:80W or less
PS-3651A Series:40W or less
30A or less
(room Temperature)
AC1,000V 20mA for 1 minute
(between charging and FG
terminals)
PS-3651A Series
0 to 50°C: without HDD
5 to 45°C: with HDD
-20 to +60°C
10%RH to 90%RH
10%RH to 90%RH
Free of corrosive gas
800 to 1,114hPa
(-300 to +2,000m)
-