Compressor System Sensor Abnormality - Daikin FTXR-T Series Service Manual

Inverter pair
Hide thumbs Also See for FTXR-T Series:
Table of Contents

Advertisement

SiUS041829E

4.19 Compressor System Sensor Abnormality

H0
Error Code
Method of Error
The system checks the DC current before the compressor starts.
Detection
Error Decision
 The voltage converted from the DC current before compressor start-up is out of the range 0.5 ~
Conditions
 The DC voltage before compressor start-up is below 50 V.
Supposed
 Broken or disconnected harness
Causes
 Defective outdoor unit PCB
Troubleshooting
Part 6 Service Diagnosis
4.5 V.
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Check the (relay) harness for the
compressor.
Is the harness broken?
NO
Turn off the power. Then, turn on
the power to restart the system.
Restart
operation and error displayed
again?
YES
YES
NO
Troubleshooting
Replace the harness.
Not a malfunction.
Keep observing.
Replace the outdoor unit
PCB (main PCB).
(R24613)
99