Outdoor Unit Pcb Abnormality - Daikin FTXR-T Series Service Manual

Inverter pair
Hide thumbs Also See for FTXR-T Series:
Table of Contents

Advertisement

Troubleshooting

4.10 Outdoor Unit PCB Abnormality

E1
Error Code
Method of Error
 The system checks if the microprocessor is working in order.
Detection
 The system checks if the zero-cross signal comes in properly.
Error Decision
 The microprocessor program runs out of control.
Conditions
 The zero-cross signal is not detected.
Supposed
 Defective outdoor unit PCB
Causes
 Noise
 Momentary drop of voltage
 Momentary power failure
Troubleshooting
84
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Turn on the power again.
Is LED A blinking?
Blink
Check if the outdoor unit is
grounded.
Grounded?
YES
∗ Before you check the LED A,
cancel the standby electricity
saving function by starting fan
operation with the remote
controller.
∗ Wait at least for 7 sec. after
turning on the power.
Continuously ON or OFF
NO
SiUS041829E
Replace the outdoor unit
PCB (main PCB).
Ground the system.
Zero-cross signal
abnormality.
Replace the outdoor unit
PCB (main PCB).
(R21201)