ID
Symbols
Message
A9
Event counter 2
Number underruns above
threshold
Maintenance required
AA
Device lifetime: Mainte‐
nance demanded
Ab
Device lifetime: Mainte‐
nance required
AC
Sensor lifetime: Mainte‐
nance demanded
AD
Sensor lifetime: Mainte‐
nance required
AE
Service: Maintenance de‐
manded
AF
Service: Maintenance re‐
quired
AG
Calibration: Maintenance
demanded
AH
Calibration: Maintenance
required
SITRANS P320/P420 (mA/HART)
Operating Instructions, 06/2018, A5E44852162-AA
Cause/Remedy
The number of underruns of the process value (set in parameters "Lower
limit" and "Monitored value") has reached the threshold.
Reset and acknowledge event counter.
Check process conditions.
Check limit monitoring and event counter settings.
Forthcoming end of configured device's lifetime.
Maintenance is strongly recommended as soon as possible.
Forthcoming end of configured device's lifetime.
Maintenance of device should be planned.
Forthcoming end of configured sensor's lifetime.
Maintenance is strongly recommended as soon as possible.
Forthcoming end of configured sensor's lifetime.
Maintenance of device should be planned.
Forthcoming end of the configured service interval.
Maintenance is strongly recommended as soon as possible.
Forthcoming end of the configured service interval.
Maintenance of device should be planned.
Forthcoming end of the calibration interval.
Maintenance is strongly recommended as soon as possible.
Forthcoming end of the calibration interval.
Maintenance of device should be planned.
Diagnostics and troubleshooting
12.2 Diagnostic messages
185