PWE high basic behaviour:
Bit
Description
15
Active parameter
14
Array
13
Parameter value can only be reset
12
Parameter value different from factory setting
11
Text available
10
Additional text available
9
Read only
8
Upper and lower limit not relevant
0-7
Data type
Active parameter is only active when communicating
through Profibus.
Array means that the parameter is an array.
If bit 13 is true, the parameter can only be reset, not
written to.
If bit 12 is true, the parameter value is different from
the factory setting.
Bit 11 indicates that text is available.
Example
STX
LGE
ADR
02
0E
01
STX =
02 Start byte
LGE =
0E Length of remaining telegram
ADR =
Sends the frequency converter on Address
1, Danfoss format
PKE =
4001; 4 in the PKE field indicates a Read
Parameter Description and 01 indicates pa-
rameter number 001, Language
IND =
0001; 1 indicates that Basic characteristics
are required.
STX
LGE
ADR
02
0E
01
PKE =
02 Start byte IND = 0001; 1 indicates that
Basic characteristics are sent
PWE
=
0405; 04 indicates that Basic behaviour as
LOW
bit 10 corresponds to Additional text. 05 is the
datatype which corresponds to Unsigned 8.
No of elements (index 2):
This function indicates the Number of elements (array)
of a parameter. The answer to the master will be in
PWE
.
LOW
Conversion and Unit of measurement (index 4):
The Conversion and unit of measurement command
indicates the conversion of a parameter and the unit of
measurement. The answer to the master will be in
PWE
. The conversion index will be in the high byte
LOW
of PWE
and the unit index will be in the low byte of
LOW
PWE
. Note that conversion index is signed 8 and
LOW
unit index is unsigned 8, see tables below.
96
PKE
IND
PWE
40 01
00 01
00 00
PKE
IND
PWE
30 01
00 01
00 00
®
VLT
5000 Design Guide
Bit 10 indicates that additional text is available. Eg.
parameter 001, Language, contains text for index field
0, English, and for index field 1, German.
If bit 9 is true, the parameter value is read-only and
cannot be changed.
If bit 8 is true, upper and lower limits of the parameter
value are not relevant.
PWE
datatype
LOW
Dec.
Datatype
3
Signed 16
4
Signed 32
5
Unsigned 8
6
Unsigned 16
7
Unsigned 32
9
Visible string
10
Byte string
13
Time difference
33
Reserved
35
Bit sequence
In this example, the master reads the Basic charac-
teristics of parameter 001, Language. The following
telegram must be sent to the frequency converter:
PWE
PCD1
HIGH
LOW
00 00
XX XX
The response from the frequency converter will be:
PWE
PCD1
HIGH
LOW
04 05
XX XX
The unit index defines the "Unit of measure". The con-
version index defines how the value should be scaled
to get the basic representation of the "Unit of meas-
ure". Basic representation is where conversion index
equals "0".
Example:
A parameter has a "unit index" of 9 and a "conversion
index" of 2. The raw (integer) value read is 23. This
means that we have a parameter of the unit "Power"
and the raw value should be multiplied by 10 to the
power of 2 and the unit is W. 23 x 10
Table for conversion and unit of measurement
®
MG.52.B2.02 - VLT
is a registered Danfoss trademark
PCD2
BCC
XX XX
XX
PCD2
BCC
XX XX
XX
2
= 2300 W