Peak voltage on motor

When a transistor in the inverter is opened, the voltage
across the motor increases by a dU/dt ratio that de-
pends on:
-
the motor cable (type, cross-section, length
screened or unscreened)
inductance
-
The natural induction causes an overshot U
motor voltage before it stabilises itself at a level which
depends on the voltage in the intermediate circuit. The
rise time and the peak voltage U
life of the motor. If the peak voltage is too high, motors
without phase coil insulation are the ones that will pri-
marily be affected. If the motor cable is short (a few
metres), the rise time and peak voltage are lower.
If the motor cable is long (100 m), the rise time and
peak voltage will increase.
If very small motors are used without phase coil insu-
lation, it is recommended to fit a sine-wave filter after
the frequency converter.
Typical values for the rise time and peak voltage
are measured on the motor terminals between
U
PEAK
two phases.
To obtain approximate values for cable lengths and
voltages not mentioned below, use the following rules
of thumb:
1. Rise time increases/decreases proportionally with
cable length.
2. U
= DC link voltage x 1.9
PEAK
(DC link voltage = Mains voltage x 1.35).
/
0.5 ×
3.
dU
dt
=
Risetime
112
in the
PEAK
affect the service
PEAK
U
PEAK
®
VLT
5000 Design Guide
Data are measured according to IEC 60034-17.
VLT 5001-5011 / 380-500 V
Cable
Mains
length
voltage
Rise time
0.5 µsec.
50 metres
500 V
1 µsec.
150 metres
500 V
0.6 µsec.
50 metres
380 V
1.33 µsec.
150 metres
380 V
VLT 5016-5102 / 380-500 V
Cable
Mains
length
voltage
Rise time
0.27 µsec.
32 metres
380 V
0.60 µsec.
70 metres
380 V
1.11 µsec.
132 metres
380 V
VLT 5122-5302 / 380-500 V
Cable
Mains
length
voltage
Rise time
0.34 µsec.
70 metres
400 V
VLT 5352-5552 / 380-500 V
Cable
Mains
length
voltage
Rise time
0.71 µsec.
29 metres
500 V
0.61 µsec.
29 metres
400 V
VLT 5001-5011 / 525-600 V
Cable
Mains
length
voltage
Rise time
0.36 µsec.
35 metres
600 V
VLT 5016-5062 / 525-600 V
Cable
Mains
length
voltage Rise time
0.38 µsec.
35 metres
575 V
VLT 5042-5352 / 525-690 V
Cable
Mains
length
voltage
25 metres
690 V
25 metres
575 V
25 metres
1)
690 V
1) With Danfoss dU/dt filter.
VLT 5402-5602 / 525-690 V
Cable
Mains
length
voltage
Rise time
0.57 µsec.
25 metres
690 V
0.25 µsec.
25 metres
575 V
1.13 µsec.
1)
25 metres
690 V
1) With Danfoss dU/dt filter.
®
MG.52.B2.02 - VLT
is a registered Danfoss trademark
Peak
voltage
dU/dt
1230 V
1968 V/µsec.
1270 V
1270 V/µsec.
1000 V
1333 V/µsec.
1000 V
602 V/µsec.
Peak
voltage
dU/dt
950 V
2794 V/µsec.
950 V
1267 V/µsec.
950 V
685 V/µsec.
Peak
voltage
dU/dt
1040 V
2447 V/µsec.
Peak
voltage
dU/dt
1165 V
1389 V/µsec.
942 V
1233 V/µsec.
Peak
voltage
dU/dt
1360 V
3022 V/µsec.
Peak
voltage
dU/dt
1430 V
3011 V/µsec.
Peak
Rise time
voltage
dU/dt
0.59 µsec. 1425
1983 V/µsec.
0.66 µsec. 1159
1428 V/µsec.
1.72 µsec. 1329
640 V/µsec.
Peak
voltage
dU/dt
1540
2.230 V/µsec.
2.510 V/µsec.
1629
1.150 V/µsec.