Danfoss VLT 5000 Series Design Manual page 30

Hide thumbs Also See for VLT 5000 Series:
Table of Contents

Advertisement

Ordering numbers, Harmonic filters
Harmonic filters are used to reduce mains harmonics
• AHF 010: 10% current distortion
• AHF 005: 5% current distortion
380-415 V, 50Hz
I
Typical
AHF,N
[kW]
10 A
4, 5.5
19 A
7.5
26 A
11
35 A
15, 18.5
43 A
22
72 A
30, 37
101 A
45. 55
144 A
75
180 A
90
217 A
110
289 A
132, 160
324 A
370 A
200
Higher ratings can be achieved by paralleling the filter units
434 A
250
578 A
315
613 A
355
648 A
400
Please note that the matching of the typical Danfoss frequency converter and filter is pre-calculated based on
400 V and assuming typical motor load (4 or 2 pole motor): VLT 5000 series is based on a max. 160 % torque
application. The pre-calculated filter current may be different than the input current ratings of VLT 5000 as stated
in the respective operating instructions, as these numbers are based on different operating conditions.
440-480 V, 60Hz
I
Typical
AHF,N
[HP]
19 A
26 A
35 A
43 A
72 A
101 A
144 A
180 A
217 A
289 A
324 A
370 A
Higher ratings can be achieved by paralleling the filter units
506 A
578 A
648 A
Please note that the matching of the typical Danfoss frequency converter and filter is pre-calculated based on
480 V and assuming typical motor load (4 or 2 pole motor): VLT 5000 series is based on a max. 160 % torque
application. The pre-calculated filter current may be different than the input current ratings of VLT 5000 as stated
in the respective operating instructions, as these numbers are based on different operating conditions.
®
MG.52.B2.02 - VLT
is a registered Danfoss trademark
Motor
Used
Danfoss ordering number
AHF 005
175G6600
175G6601
175G6602
175G6603
175G6604
175G6605
175G6606
175G6607
175G6608
175G6609
175G6610
175G6611
175G6688
Motor
Used
Danfoss ordering number
AHF 005
10, 15
175G6612
20
175G6613
25, 30
175G6614
40
175G6615
50, 60
175G6616
75
175G6617
100, 125
175G6618
150
175G6619
200
175G6620
250
175G6621
300
175G6689
350
175G6690
450
500
600
®
VLT
5000 Design Guide
AHF 010
175G6622
175G6623
175G6624
175G6625
175G6626
175G6627
175G6628
175G6629
175G6630
175G6631
175G6632
175G6633
175G6691
Two 217 A units
Two 289 A units
289 A and 324 A units
Two 324 A units
AHF 010
175G6634
175G6635
175G6636
175G6637
175G6638
175G6639
175G6640
175G6641
175G6642
175G6643
175G6692
175G6693
217 A and 289 A units
Two 289 A units
Two 324 A units
VLT 5000
5006, 5008
5011
5016
5022, 5027
5032
5042, 5052
5062, 5072
5102
5122
5152
5202, 5252
5302
5352
5452
5502
5552
VLT 5000
5011, 5016
5022
5027, 5032
5042
5052, 5062
5072
5102, 5122
5152
5202
5252
5302
5352
5452
5502
5552
29

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents