Other connections
Schemes of electric wiring – motors of fans
Three-phase asynchronous motor with thermistors
Three-phase EC motor
Single-phase asynchronous motor with thermistors
Single-phase EC motor with 10 poles
Single-phase asynchronous motor (up to 0.75 kW) with thermistors
controlled by the single-phase Danfoss FC051 frequency inverter, IP21, (up to 0.75 kW), Modbus
Air Handling units AeroMaster XP
U1,V1,W1,PE
- clamps of triple-phase motor power supply.
3f-400V/50Hz
K1, K2
– thermistor clamps
PE, L1, L2, L3
– power supply clamps
of the triple-phase motor
3f-400V/50Hz
11, 14 – fan summary fault
E1 – DC input
D1 – digital input (on/off)
24 V – 24 V DC voltage source
10 V – 10 V DC voltage source
GND – ground
U1, U2, PE
– svorky napájení jednofázového motoru
1f-230V/50Hz
K1, K2
– thermistor clamps
PE, N, L
– power supply clamps of the single-phase motor
1f-230V/50Hz
11, 14 – fan summary fault
E1 – DC input
D1 – digital input (on/off)
24 V – 24 V DC voltage source
10 V – 10 V DC voltage source
GND – ground
Frequency converter power supply
Three-phase asynchronous two-speed motor with thermistors
Three-phase PMBlue motor
Single-phase EC motor up to 10 poles
U1, V1, W1, PE1
- power supply clamps of the triple-phase single speed motor 3ph.-400V/50Hz
K1, K2
– thermistor clamps
L1, N, PE
- clamps of single-phase frequency inverter power supply 1ph.-230/50Hz
29, 50
- frequency inverter terminals for the motor's thermo-contact (TK) connection
61, 68, 69
- Modbus bus terminals
Frequency converter data settings have been set by the manufacturer
Modbus
U1,V1,W1,PE
- clamps of 1. winding of triple-phase double
speed motor power supply. 3f-400V/50Hz (s. 1)
U2,V2,W2
- clamps of 2. winding of triple-phase double
speed motor power supply. 3f-400V/50Hz (s. 2)
K1, K2
– thermistor clamps
PE, L1, L2, L3
– power supply clamps of the triple-
phase motor 3f-400V/50Hz
11, 14 – fan summary fault
E1 – DC input
D1 – digital input (on/off)
24 V – 24 V DC voltage source
10 V – 10 V DC voltage source
GND – ground
PE, N, L
– power supply clamps of the
single-phase motor 1f-230V/50Hz
11, 14 – fan summary fault
E1 – DC input
D1 – digital input (on/off)
24 V – 24 V DC voltage source
10 V – 10 V DC voltage source
GND – ground
A1 – output of the
tachogenerator – operation
A2 – tacho výstup – state