Air-handling units modifi ed for clean plants and health service
Section connection
Th e sections can be assembled together by connecting their base
frames and connecting the respective sections.
Before putting together and connecting the sections, it is
necessary to paste the rubber sealing (19x4) on the contact
surfaces of the connecting frame.
When connecting two chambers fi tted with adjacent condensate
drainage trays, it is necessary to paste the rubber sealing (19x4) on
the contact surfaces of both trays.
For the recommended installation procedure for adjustable or
fi xed frame feet, refer to a separate section.
Th e chambers must be situated as close as possible during
assembly. To pull them together, you can use the base frame
connection. Sections without base frames can be pulled together
using fastening belts with a ratchet mechanism. Th e belts must be
situated in the lower part as close as possible to the lower panel.
Th e base frames are connected using M10x120 screws.
Th e chambers are connected together using M6x40 hexagon-head
screws inserted into the prepared holes in the connecting frame.
Th e connecting frame is always equipped with though holes on
one side while the holes on the other side are fi tted with riveted
nuts. All the screws are accessible from inside the unit and there
is no need to remove the rear panels. Th ey are sealed with sealant
around the entire perimeter from inside the unit.
Th e inner chamber connection is intended to provide fi nal
connection. Never use it to pull the chambers together.
A conductive interconnection must be ensured using grounding
connections when connecting the chambers.
Unused connecting frame holes must be plugged to prevent
undesirable leakage of transported air through them and
contamination of the interior of the frame sectional cross
members.
Figure 1 – Connection of chambers using the
connection frame
Screw
connection
inside the
chamber
Once installation has been completed, all the gaps in the
connections must be checked and sealed to prevent fouling and
dirt deposits building in gaps and to make it easy to clean all the
surfaces.
For sealing, use only sanitary fungicidal (biocidal) sealant. Sealant
is a part of the delivery. Sealant must only be applied on a clean
surface..
Air Handling units AeroMaster XP
Figure 2 – Sealing at the connection point of the
Figure 3
Filter assemblies, Replacement of fi lter inserts
Figure
Chamber
Chamber
sealing
sealing
Fungicidal – destroys parasitic fungi and mildew
Biocidal – includes one or more active substances which destroy, repulse or eliminate
harmful organisms; prevents biodegradation by eliminating bacteria, yeasts and fungi
condensate drainage trays
Seal the
chamber
connection gaps
Sliding fi lter assembly for XP 04, XP 06 and XP10
4 – Removal of fi lter insert equipped with
a sliding frame (XP04 – XP10)
1
2
47