XPRJ and XPRF Sections

XPRJ (for control system built-in assembly)
XPRF (for frequency converter/s)
Figure 1 - control system assembly section
Chamber inner ventilating aperture
equipped with a filter insert (outlet)
Assembly supporting holed profile
D29 for rubber grommets
Chamber inner
ventilating aperture
Power cable grommets
Main switch and main power supply terminal box (only XPRJ)
General Warnings
When handling, installing, wiring, commissioning, repairing or
servicing this device, it is necessary to observe valid safety rules,
standards and generally recognized technical rules. Every device
connection must comply with the respective safety standards. The
device must be used only as intended and in accordance with this
documentation and the documentation of related assemblies - control
units and frequency converters. No changes influencing the device
safety can be made without the permission of the manufacturer/
supplier. Keep this document for further use!
XPRJ Section Intended Use
The XPRJ section is designed for control unit assembly which supplies
and controls the AeroMaster XP air-handling unit. The section is
provided with a main switch.
XPRF (Frequency Converter) Section
Intended Use
The XPRF section is designed for the AeroMaster air-handling unit
frequency converter assembly.
Wastes and Waste Classification
In case of final unit liquidation of the product or any part, it is neces-
sary to observe the respective national environmental protection and
waste disposal regulations. Follow the rules of sorted waste disposal,
respect differences in material and their composition (metals, plastics,
electrical parts, mineral wool, etc).
It is advisable to hire a provider specialized in the waste disposal of
these materials.
Air Handling units AeroMaster XP
Side
Covering panel IP20
cover
(only XPRJ)
Service
door
space
for cabling
M&C cable grommets
Basic Data (ČSN EN 60439-1)
Classification: One-chamber covered case equipped
with solid parts intended for a particular use.
Installation: The case can be built into the AeroMaster XP
air-handling unit.
Standards: IEC 60439-1, ČSN EN 62208
(IEC 62208:2002)
Covering:
- A metal (galvanized) case built into the XP section,
accessible through the service door and covering panel
which can be removed only using tools (XPRJ).
- A metal (galvanized) case built into the XP section,
accessible through the service door (XPRF).
Degree of protection – door closed: IP 44
Degree of protection – door open: IP 20 (XPRJ) / IP20 (XPRF)*
* The case itself IP00, frequency converters IP20.
Operating conditions: Indoor installations 0 °C to +35 °C,
outdoor installations -40 °C to 50 °C (with accessories).
Storage:
-30 °C to +70 °C (XPRJ),
-25 °C to +65 °C (XPRF)
Max. relative humidity 85%,
Without condensation and frost deposit.
Grounding system: PE conductor
Dimensions: see the section description.
Weight: see the section description.
Types of electrical connections of functional units: FFF
EMC - incl. integrated assemblies: environment 1
25