XPRJ and XPRF Sections
Figure 2 - Section cable departures
Wiring Procedure:
The wiring diagram (incl. cabling) and Installation, Commissioning and
Operating Instructions are included in the accompanying documenta-
tion of the control unit; it is also necessary to use the AeroMaster XP
Installation, Commissioning and Operating Instructions.
General Procedures for Wiring:
Connect power elements.
Connect M&C elements.
Check the installation of the air-conditioning unit
(if delivered).
Connect the air-conditioning unit heater section
(see Accessories).
Lead the main power supply (cable harness dimensioned for the
total input current of the air-handling unit) to the main switch
terminal box on the section panel.
Check the completed wiring.
Check the tightening of the cable grommets, and blind those
unused.
Perform the electrical equipment initial inspection.
Note:
To mount the cables and wiring harness inside the section, use the
rubber grommets installed in the openings of the assembly supporting
profile to avoid damage to the cable insulation, see figure # 29.
Safety
When performing any work, repairs or maintenance, the device
must always be disconnected from the power supply.
When planning or installing the air-handling unit, observe norma-
tive requirements for safe access to the air-handling unit.
When reinstalling the covers (front or side covers) also restore
their conductive connections (properly tighten the screws using
fan washers).
Maintain the prescribed degree of protection.
Maintenance
XPRJ/XPRF sections do not require any special maintenance if
installed in the intended environment.
Any damage to the surface protecting galvanized layer (zinc 275
g/m
2
) must be repaired immediately with priming paint (S2013) to
avoid corrosion.
Depending on the operating conditions, regularly check the filter
inserts of the chamber inner ventilating apertures
28
Figure 3 – Cabling inside of the box
Cables leading into the
section through cable
Unused cable grommets
must be blinded.
Recommended run of
cables in the cable trench.
Lockable main switch with
a terminal box to connect
the main power supply on
the XPRJ section panel.
Accessories
The set of heating elements (AC 230V/50Hz, 400W) consists of one
or more compact resistance elements with a heat radiator made of
electrolytically oxidized aluminium profile and
a fan (45 m
against overheating if the fan fails.
Figure 4 - Air-conditioning box
Heating elements to keep the minimum prescribed temperature
inside the chamber; a set according to the XP air-handling unit size
to be installed on the DIN bar inside the section
 Set of heating elements for temp. range from -25 °C
 Set of heating elements for temp. range from -40 °C
The 620 W chamber air-conditioning unit is to be mounted on the
service door of the section; designed for indoor and outdoor instal-
lations (-20 °C / +55 °C).
Set of filter inserts for chamber ventilating apertures.
Filtering textile cuts, 125 x 125 mm.
3
/h). Safety switch of the heating element - to protect it
Connection using the thermo-contact
Degree of protection: IP20
Protection Class: grounding
Max. surface temperature: 75 °C