Schemes Of Electric Wiring - Remak AeroMaster FP Series Service Instructions Manual

Air handling units
Table of Contents

Advertisement

Other connections
Schemes of electric wiring - motors of fans
2 Triple-phase motors (2x, up-to 1,1 kW)
TK1, TK1
- clamps of the 1st motor thermocontacts
TK2, TK2
- clamps of the 2nd motor thermocontacts
Single phase motor (up-to 0,5 kW)
controlled by single-phase frequency inverter (up to 0,5 kW), Modbus
Single phase motor (1,5 kW)
controlled by three-phase frequency inverter, IP21 (1,5 kW), Modbus
Single phase motor (up-to 2x 1,1 kW)
controlled by three-phase frequency inverter, IP21/IP54 (up to 2,2 kW), Modbus
8
U1, V1, W1, PE1
- power supply clamps of the 1st triple-
phase single speed motor 3ph.-400V/50Hz
U2, V2, W2, PE2
- power supply clamps of the 2nd triple-
phase single speed motor 3ph.-400V/50Hz
Frequency inverter power supply
Modbus
Frequency inverter power supply
Modbus
Frequency inverter power supply
Air handling units
2 Triple-phase motors (2x, up-to 1,1 kW)
U1,V1,W1,PE
- clamps of triple-phase motor power supply.
3ph.-400V/50Hz
TK,TK
- clamps of motor thermocontacts
U1, V1, W1, PE1
- power supply clamps of triple-phase single speed motor 3ph.-400V/50Hz
TK, TK
- clamps of the motor thermocontacts
L1, N, PE
- clamps of single-phase frequency inverter power supply 1ph.-230/50Hz
29, 50
- frequency inverter terminals for the motor's thermo-contact (TK) connection
61, 68, 69
- Modbus bus terminals
Frequency converter data settings have been set by the manufacturer
U1, V1, W1, PE1
- power supply clamps of the triple-phase single speed motor 3ph.-400V/50Hz
TK, TK
- clamps of the 1st motor thermocontacts
TK2, TK2
- clamps of the 2nd motor thermocontacts
L1, L2, L3, PE
- clamps of three-phase frequency inverter power supply 3ph.-400V/50Hz
29, 50
- TK clamps of frequency inverter
61, 68, 69
- Modbus bus terminals
Frequency converter data settings have been set by the manufacturer
U1, V1, W1, PE1
- power supply clamps of the 1st triple-phase single speed
motor 3ph.-400V/50Hz
U2, V2, W2, PE2
- power supply clamps of the 2nd triple-phase single speed
motor 3ph.-400V/50Hz
TK1, TK1
- clamps of the 1st motor thermocontacts
TK2, TK2
- clamps of the 2nd motor thermocontacts
L1, L2, L3, PE
- clamps of triple-phase frequency inverter power supply
3ph.-400V/50Hz
29, 50
- TK1 (1st motor) clamps and TK2 (2nd motor) clamps of
frequency inverter
61, 68, 69
- Modbus bus terminals
Frequency converter data settings have been set by the
Modbus
manufacturer

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aeromaster fp 4.0Aeromaster fp 2.7

Table of Contents