Monitoring Of The Device; Monitoring Functions - Siemens SIMATIC IPC647E Operating Instructions Manual

Hide thumbs Also See for SIMATIC IPC647E:
Table of Contents

Advertisement

5.5

Monitoring of the device

5.5.1

Monitoring functions

You can monitor the following device functions with the SIMATIC DiagBase or SIMATIC
DiagMonitor software:
Monitoring
Description
Temperature monitor-
ing
Fan monitoring
The fans are monitored at the following positions:
Watchdog
SIMATIC IPC647E
Operating Instructions, 11/2018, A5E45589180-AA
Monitoring for temperature high and low limits as well
as cable breaks of the temperature sensors
Temperature sensors record the temperature at
critical device points, e.g. at the processor.
The temperature thresholds are defined for the indi-
vidual temperature sensors.
With SIMATIC IPC DiagBase or SIMATIC IPC Diag-
Monitor, actions are triggered when the temperature
thresholds are exceeded.
Monitoring for underspeed and fan failure as well as
cable breaks of the speedometer cable
Front panel
Processor
Triple Head graphics card
Power supply (non-redundant)
Drive cage type A
Monitoring of the system status and message to
determine if a station is still operational
If the watchdog is not addressed within a configured
monitoring time, a watchdog alarm is output.
A change to the monitoring time is effective immedi-
ately.
Operating the device
5.5 Monitoring of the device
Status displays and actions
Status display "TEMP (Page 24)"
Speed control of the device fans,
the power supply fan and the fan of
the optional graphics card
Temperature alarm is generated.
Status display "FAN (Page 24)"
Fan alarm is output.
Status display "WATCHDOG
(Page 24)"
Depending on the setting, the following
actions are triggered:
Reset on: Hardware reset is per-
formed
Reset off: No action is performed
The device is restarted.
The device is shut down.