4. Specifications
Working Voltage
Voltage measurement
Current measurement
Frequency measurement
Revolution measurement
Output
Ambient temperature
KP310V1.0 Controller Operation Manual
12VDC (8~16VDC)
AC Input Voltage:
Phase voltage 10~290VAC RMS
Precision level:2.0
Three-phase four-line
Three-phase three-line
Single-phase two-line
Double-voltage output simultaneously
Double-voltage output alternative
Primary current:
1A -900A (Parameters Set)
Secondary current:
5mA
Precision level:
2.0
Frequency range:
20~70HZ(voltage>15V)
Precision level:
0.5
Voltage range:
5-50V
Max. frequency:
10000Hz
Flywheel tooth:
1-500
Fuel output relay:
15A/12VDC
Start output relay:
15A/12VDC
Preheat output relay:
5A/12VDC
Configuration output relay Ⅰ:
5A/12VDC
Configuration output relay Ⅱ:
5A/12VDC
-20~70℃