If there is no operation for more than 60s, system will automatically exit Parameter Set menu, and
enter the System Operation menu.

8.1 Parameters Set list

Parameter Code
Data
No.
Parameters
Engine
1
Flywheel Gears
2
Tripping speed
Tripping
3
frequency
Tripping
4
charging voltage
5
Starting timer
Tripping oil
6
pressure delay
Maximum
7
starting time
8
Under RPM
9
Over RPM
Under RPM
10
fault delay
Over RPM fault
11
delay
Engine Stop To
12
Start Delay
R
R
A
A
V
V
RUN
RUN
V
V
O
O
Code
Range
Accuracy Defaults
○○○○○●
1-500
○○○○●○
0-3000
○○○○●●
0-600
○○○●○○
0-400
○○○●○●
1-100
○○○●●○
1-100
○○○●●●
1-100
○○●○○○
0-6000
○○●○○●
0-6000
○○●○●○ 0-65535
○○●○●● 0-65535
○○●●○○ 10-65535
- 16 -
KP310V1.0 Controller Operation Manual
Model KP310V1.0
Model KP310V1.0
1
100
Engine RPM when starter is
1rpm
600
tripping
Genset Frequency when starter is
0.1Hz
200
tripping
Charging alternator voltage when
0.1V
50
starter is tripping
0.1s
5
Genset start timer
Oil pressure when starter is tripper
0.1s
5
Average starter working Time
0.1s
30
1rpm
0
Engine under speed
1rpm
1600
Engine over speed
Engine under speed delay
0.1s
0
Engine over speed delay
0.1s
0
Engine Stop to start delay timer
0.1s
30